The installation requirements for power distribution boards (or cabinets) are as follows: They must be constructed from non-combustible materials. In office spaces or production areas with a low risk of electric shock, open-type distribution boards may be used. In environments with a high risk of electric shock or adverse working conditions-such as processing workshops, foundries, forging shops, heat-treatment facilities, boiler rooms, or woodworking shops-enclosed cabinets must be installed. In hazardous areas where conductive dust is present or flammable/explosive gases may be generated, sealed or explosion-proof electrical equipment is mandatory.
All electrical components, instruments, switches, and wiring within a distribution board (or cabinet) must be arranged neatly, installed securely, and positioned for convenient operation. For floor-mounted units, the base should be elevated 5–10 mm above the floor. Operating handles should generally be positioned at a height of 1.2–1.5 meters. A clear space of 0.8–1.2 meters must be maintained in front of the board (or cabinet), free from any obstructions. Protective grounding (or bonding) conductors must be reliably connected. No live, uninsulated parts may be exposed outside the enclosure. Any electrical components that must be mounted on the exterior surface of the cabinet or board must be provided with reliable protective shielding.